The Messana system can show seven buffer tank alarms and warnings. They cover the tank probe, the tank temperature, and the heat or cool sources that charge the tank. Most of these alarms need electrical and/or hydronic expertise to fix, so we recommend contacting your installer.
The guide below explains what each one means and how to solve it.
Code | Alarm | Category | Stops tank charging? |
|---|---|---|---|
TNK-001 | Temperature probe failure | Error | Yes |
TNK-002 | High temperature | Error | Yes |
TNK-003 | Anti-freeze warning | Warning | No, it starts charging |
TNK-004 | Anti-freeze alarm | Error | Not currently used |
TNK-005 | No energy resource available | Error | Yes |
TNK-006 | No energy resource switched on | Warning | Yes |
TNK-007 | DHW conflict on shared diverting valve | Warning | Only some sources |
Temperature probe failure (TNK-001)
Category: Error
Description: The system cannot read the buffer tank temperature. Either the probe input returns no valid value, or no input is assigned to the tank in the configuration. This is a blocking error: without a temperature, the tank sends no energy request and anti-freeze protection cannot start. The high temperature (TNK-002) and anti-freeze (TNK-003) checks are also switched off while it is active.
Common causes:
- The tank probe is disconnected, broken or short-circuited.
- The probe wiring is interrupted or connected to the wrong terminal.
- The expansion module that reads the probe is not communicating (EXP-001). After about 10 failed cycles, all its probe readings become invalid.
- The configuration assigns the tank to an input that doesn’t exist on the expansion module, or assigns no input at all.
Resolution: Measure the probe and its wiring at the expansion module terminal. If the expansion module also shows a communication error (EXP-001), fix that first. Then check in the configuration that the tank probe is assigned to the input it is actually wired to. The alarm clears by itself as soon as a valid temperature is read.
High Temperature (TNK-002)
Category: Error
Description: In heating, the buffer tank temperature has reached its high temperature limit. While the alarm is active, the tank stops requesting energy, unless anti-freeze protection is running. The alarm clears as soon as the temperature drops below the limit, so it can turn on and off repeatedly if the tank sits right at the limit.
Common causes:
- A heat source keeps heating the tank above the limit. It may not be following its target, or another system may be driving it.
- The high temperature limit is set too close to the tank’s target temperature.
- The tank probe reads too high because of its position or a fault.
Resolution: Check the supply temperature of the heat sources that serve the tank, and whether another controller is also driving them. Check that the high temperature limit leaves enough margin above the tank’s heating target. Compare the tank probe reading with a reference thermometer. The alarm clears by itself when the temperature drops below the limit.
Anti-freeze Warning (TNK-003)
Category: Warning
Description: In heating, the buffer tank temperature has dropped to or below the anti-freeze temperature. The warning appears only after more than one hour has passed since the last heating/cooling changeover. If anti-freeze protection is enabled, the tank requests energy to warm back up, even when the system is switched off. If anti-freeze protection is disabled, this is a warning only. The warning clears as soon as the temperature rises above the anti-freeze temperature, so charging stops just above that point.
Common causes:
- The tank has not been charged for a long time in a cold space, for example because it is off or has no requests.
- The heat sources serving the tank are unavailable.
- The anti-freeze temperature is set higher than the tank’s normal standby temperature.
- The tank probe reads too low.
Resolution: If you want the tank to protect itself, check that anti-freeze protection is enabled. Check the heat sources that serve the tank and any alarms they show. Check that the anti-freeze temperature is set sensibly, and compare the tank probe reading with a reference thermometer. The warning clears by itself when the temperature rises above the anti-freeze temperature.
Anti-freeze alarm (TNK-004)
Category: Error
Description: This alarm is meant to appear when the anti-freeze warning (TNK-003) lasts longer than a set time. It is not raised by the current software, so you should not see it in the app.
Resolution: If the tank stays cold for a long time, follow the steps for the anti-freeze warning (TNK-003): check anti-freeze protection, the heat sources serving the tank, and the tank probe.
No Energy Source Available (TNK-005)
Category: Error
Description: At least one heat or cool source serving the tank is switched on in the app, but none of them can actually run for the current season. They may be disabled by the system, below their temperature limit, or busy producing domestic hot water. No source is started for the tank. This alarm does not turn the tank’s alarm flag red in the app, so check the alarm list directly.
Common causes:
- The sources serving the tank are disabled by the system, for example because they are in alarm or have a communication error.
- In heating with more than one source, some sources are held off because they are below their temperature limit.
- In multi-stage operation, the sources are busy producing domestic hot water.
Resolution: Check and resolve the alarms of each source that serves the tank. Make sure at least one of them can run in the current season. The alarm clears by itself as soon as a source becomes available.
No Energy Resource Switched On (TNK-006)
Category: Warning
Description: None of the heat or cool sources that can serve the tank in the current season is switched on in the app. The same warning stays on permanently if no source is assigned to the tank. No source is started for the tank. Like TNK-005, it does not change the tank’s alarm flag in the app.
Common causes:
- All the tank’s sources for the current season are switched off in the app.
- The sources assigned to the tank can’t run in the current season.
- No source is assigned to the tank, but the tank is set to manage its own sources.
Resolution: Switch on at least one of the tank’s sources in the app. Check in the configuration that the tank’s sources can run in the current season. If the sources are controlled by an external system, set the tank so it does not manage them. The warning clears by itself as soon as a source is available.
DHW Conflict on Shared Diverting Valve (TNK-007)
Category: Warning
Description: The tank tried to start a heat source that shares a domestic hot water (DHW) diverting valve with other sources, while one of them was producing hot water. The tank skips the sources in that group until the DHW cycle ends; its other sources keep running. The warning only appears if the conflict starts while the tank is calling. It can also stay on after the conflict ends if the DHW cycle finishes while the tank is idle.
Common causes:
- Hot water production is running on a source in the shared valve group while the tank is calling for energy.
- The warning is left over from an earlier conflict that ended while the tank was idle.
Resolution: Wait for the DHW cycle to end. The tank’s sources in the group are released when it does. If the warning stays on with no DHW cycle running, it is left over: it clears at the end of a later conflict or when the control restarts. If conflicts happen often, review which sources share the DHW diverting valve.
If you still see a buffer tank alarm or warning after these checks, contact your installer or open a support case with Messana support. Include the alarm code in your message.