The Messana system can show two pump alarms: a communication error, when the controller can’t reach the pump, and a pump alarm, when the pump itself reports a fault. Neither one stops the pump on its own: the control keeps running the pump while they are active. These alarms usually need electrical and/or hydronic expertise to fix, so we recommend contacting your installer.
The guide below explains what each one means and how to resolve it.
Communitcation Error (PMP-001)
Category: Error
Description: The system sent a request to a WILO pump over the RS-485 bus and got no answer. The alarm appears at the first missed answer, with no delay. This fault doesn’t block the system: the control keeps calculating when the pump should run, and no other alarm follows from it. While the pump is not answering, the system retries less often. The last readings and warnings from the pump (PMP-003 and PMP-004) stay on screen and may be out of date.
Common Causes:
- The pump is powered off.
- The RS-485 wiring is disconnected or damaged, the A and B wires are swapped, or the bus termination is missing.
- The Modbus address or serial port set for the pump in the configuration doesn’t match the pump.
- A pump is set as a WILO model in the configuration but is not actually controlled over the bus, or is wired to the other serial port. The system still polls it, so it reports a communication error.
Pump Alarm (PMP-002)
Category: Error
Description: The alarm contact wired from the pump to an expansion module input is active. This is usually the fault output of the pump or of its thermal protection. On a twin pump, either body can raise it. This fault doesn’t block the system: the control keeps running the pump while the alarm is active, so check the pump promptly.
Common causes:
- A real pump fault: motor overload, thermal protection tripped, blocked rotor or dry running.
- A problem with the pump’s power supply.
- A wiring fault on the alarm input.
- The wrong contact polarity in the configuration. The input can be set to alarm when the contact is closed or when it is open.
- The expansion module that reads the input is not communicating (EXP-001). After about 10 failed cycles its inputs read as open. If the contact is set to alarm when open, the pump alarm appears without any real pump fault.
Resolution: Check the pump itself: power supply, thermal protection, rotor and water in the circuit. Then check the wiring of the alarm input and the contact polarity set in the configuration. If the expansion module that hosts the input also shows a communication error (EXP-001), fix that first. The alarm clears by itself when the contact returns to its normal state.